9.16.2.1. |
Required Installation of Granular Material
- Except as provided in Sentence (2), not less than 100 mm of coarse clean granular material containing not more than 10% of material that will pass a 4 mm sieve shall be placed beneath floors-on-ground. (See also Subsection 9.13.4. and Note A-9.13.4.)
- Granular material need not be installed under
- slabs in garages, carports or accessory buildings, or
- buildings of industrial occupancy where the nature of the process contained therein permits or requires the use of large openings in the building envelope even during the winter.
|