9.17.2. General

9.17.2. General
9.17.2.1. Location
  1. Columns shall be centrally located on a footing conforming to Section 9.15.
9.17.2.2. Lateral Support
  1. Columns shall be securely fastened to the supported member to reduce the likelihood of lateral differential movement between the column and the supported member. (See also Article 9.23.6.2.)
  2. Except as permitted by Sentence (3), columns shall be laterally supported to resist racking
    1. directly, or
    2. by connection to the supported members. (See Note A-9.17.2.2.(2).)
  3. Columns need not be provided with lateral support as described in Sentence (2), where
    1. the distance from finished ground to the underside of the joists is not more than 600 mm, and
    2. the columns support a deck with no superstructure.