9.20.13. Control of Rainwater Penetration

9.20.13. Control of Rainwater Penetration
9.20.13.1. Materials for Flashing
  1. Materials used for flashing shall conform to Table 9.20.13.1.

    Table 9.20.13.1.
    Flashing Materials

    Forming Part of Sentence 9.20.13.1.(1)

    Table 9.20.13.1. Flashing Materials

  2. Aluminum flashing in contact with masonry or concrete shall be effectively coated or separated from the masonry or concrete by an impervious membrane.
9.20.13.2. Fastening of Flashing
  1. Fastening devices for flashing shall be corrosion-resistant and, where metal flashing is used, shall be compatible with the flashing with respect to galvanic action.
9.20.13.3. Location of Flashing
  1. Flashing shall be installed in masonry and masonry veneer walls
    1. beneath jointed masonry window sills,
    2. over the back and top of parapet walls,
    3. over the heads of glass block panels,
    4. beneath weep holes, and
    5. over the heads of window or door openings in exterior walls when the vertical distance between the top of a window or door frame and the bottom edge of the eave exceeds one-quarter of the horizontal eave overhang.
9.20.13.4. Extension of Flashing
  1. When installed beneath jointed masonry window sills or over the heads of openings, flashing shall extend from the front edge of the masonry up behind the sill or lintel.
9.20.13.5. Flashing for Weep Holes in Masonry/Masonry Walls
  1. Flashing beneath weep holes in cavity walls and masonry veneer/masonry backing walls shall
    1. be bedded not less than 25 mm in the inside wythe,
    2. extend to not less than 5 mm beyond the outer face of the building element below the flashing, and
    3. be installed with a nominally horizontal slope toward the outside wythe.
9.20.13.6. Flashing for Weep Holes in Masonry Veneer
  1. Flashing beneath weep holes in masonry veneer over masonry backing walls shall conform to the flashing requirements for cavity walls and masonry veneer/masonry backing walls in Article 9.20.13.5.
  2. Flashing beneath weep holes in masonry veneer over wood-frame walls shall be installed so that it extends from a point not less than 5 mm beyond the outer face of the building element below the flashing to a point 150 mm up the wood-frame wall.
  3. Where the frame wall is sheathed with a sheathing membrane, a non-wood-based rigid exterior insulating sheathing or a semi-rigid insulating sheathing with an integral sheathing membrane, the flashing shall be installed behind the sheathing membrane or insulating sheathing.
  4. Flashing described in Sentence (2) is permitted to conform to the requirements for concealed flashing in Table 9.20.13.1.
9.20.13.7. Flashing Joints
  1. Joints in flashing shall be made watertight.
9.20.13.8. Required Weep Holes
  1. Weep holes spaced not more than 800 mm apart shall be provided at the bottom of
    1. cavities in cavity walls, and
    2. cavities or air spaces in masonry veneer walls.
  2. The cavities or air spaces described in Sentence (1) shall include those above lintels over window and door openings required to be flashed in conformance with Article 9.20.13.3.
9.20.13.9. Protection of Interior Finish
  1. Except as provided in Sentence (3), where the interior finish of the exterior walls of a building is a type that may be damaged by moisture, exterior masonry walls, other than cavity walls or walls that are protected for their full height by a roof of a carport or porch, shall be covered on the interior surface with sheathing membrane conforming to CAN/CGSB-51.32-M, "Sheathing, Membrane, Breather Type," lapped not less than 100 mm at the joints.
  2. In situations described in Sentence (1), flashing shall be provided where water will accumulate, to lead it to the exterior.
  3. Where insulation that effectively limits the passage of water is applied by a waterproof adhesive or mortar directly to parged masonry, the requirements for sheathing membrane in Sentence (1) do not apply. (See Note A-9.20.13.9.(3).)
9.20.13.10. Mortar Droppings
  1. Cavity walls shall be constructed so that mortar droppings are prevented from forming a bridge to allow the passage of rain water across the cavity.
9.20.13.11. Caulking at Door and Window Frames
  1. The junction of door and window frames with masonry shall be caulked in conformance with Subsection 9.27.4.
9.20.13.12. Drips beneath Window Sills
  1. Where no flashing is installed beneath window sills, such sills shall be provided with a drip not less than 25 mm from the wall surface.