9.20.15. Reinforcement for Earthquake Resistance

9.20.15. Reinforcement for Earthquake Resistance
9.20.15.1. Amount of Reinforcement
  1. Where reinforcement is required in this Section, masonry walls shall be reinforced horizontally and vertically with steel having a total cross-sectional area of not less than 0.002 times the horizontal cross-sectional area of the wall, so that not less than one-third of the required steel area is installed either horizontally or vertically and the remainder in the other direction.
9.20.15.2. Installation Standard
  1. Where reinforcement for masonry is required in this Section, it shall be installed in conformance with the requirements for reinforced masonry as contained in CSA A371, "Masonry Construction for Buildings."