6.3.4. Ventilation for Laboratories

6.3.4. Ventilation for Laboratories
6.3.4.1. Application
  1. This Subsection applies to laboratories where dangerous goods, including flammable liquids and combustible liquids, are used in normal laboratory operations in quantities or in a manner that creates a fire or explosion hazard.
6.3.4.2. General Ventilation
  1. A laboratory shall be provided with continuous mechanical ventilation designed to ensure that dangerous goods vapours and particles
    1. do not accumulate in the laboratory,
    2. are prevented from migrating to other parts of the building,
    3. do not accumulate in the ventilation system,
    4. are exhausted to the outdoors, and
    5. are not returned to the building.
  2. A ventilation system required by this Subsection shall be provided with monitoring devices to
    1. indicate that the ventilation system is in operation, and
    2. sound an alarm if the ventilation system is malfunctioning.
  3. A ventilation system required by this Subsection shall be maintained in conformance with Article 5.5.4.1. of Division B of the NFC.
6.3.4.3. Enclosure Exhaust Ventilation
  1. The ventilation system for a power-ventilated enclosure required by Sentence 5.5.4.2.(1) of Division B of the NFC shall
    1. conform to NFPA 91, "Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids,"
    2. provide continuous exhaust ventilation at an air velocity sufficient to prevent the accumulation of combustible or reactive deposits in the power-ventilated enclosure and its exhaust duct system,
    3. confine dangerous goods vapours and particles to the area where they are generated and exhaust them to the outdoors,
    4. not return the exhausted air to the building, and
    5. be provided with well identified control switches that are
      1. located outside of the power-ventilated enclosure, and
      2. readily accessible in case of an emergency.
6.3.4.4. Enclosure Construction
  1. The power-ventilated enclosure required by Sentence 5.5.4.2.(1) of Division B of the NFC and its exhaust duct system shall
    1. except as provided in Sentences (2) and (3), be constructed of noncombustible materials compatible with and chemically resistant to the dangerous goods vapours and particles being exhausted, and
    2. be provided with access doors to permit inspection and maintenance of the fan assembly and exhaust ducts.
  2. Combustible materials are permitted in systems described in Clause (1)(a) if
    1. such materials are required by the corrosive or reactive properties of the dangerous goods being used, and
    2. their flame-spread rating is not more than 25.
  3. The flame-spread rating required by Sentence (2) is permitted to be greater than 25 if an automatic fire suppression system is provided inside the power-ventilated enclosure and its exhaust duct system.