Older furnace equipment typically draws its combustion air from within the mechanical room and exhausts flue gases through a vent that terminates at the roof level. Replacing an older furnace with a new, high-efficiency condensing unit typically involves installing a new plastic exhaust vent and combustion air pipe that terminate on the outside of the home (Figure 3).
In practice, installing this two-pipe venting can be challenging particularly where the existing furnace appliance is located in the centre of a finished home or where the creation of new wall or roof penetrations is difficult or undesirable. As a result, "band-aid" solutions are often applied in an attempt to satisfy the venting and combustion air requirements of high-efficiency furnaces.
The following practices are not consistent with quality furnace installations and are not compliant with the FortisBC Furnace and Boiler Replacement Program requirements:
The new venting must comply with ULC-S6362 and consist "entirely of factory-made parts, each designed to be assembled with the others..." in order to be compliant with CSA B149.1 - Natural Gas and Propane Installation Code. Combining venting materials from different manufacturers including pipes, fittings, primers, and cements is not ULC S636 compliant. Poor seals at venting joints is a safety concern and may result in flue gas leakage.
In many installation scenarios, routing the new plastic piping through an existing chimney is more favourable than other pathways. While this practice can be acceptable under some conditions, the venting must be adequately supported along its length (Figure 4). Per CSA B149.1 - Natural Gas and propane installation code, the new venting must be supported independently of the furnace appliance. Additionally, the entry point of the plastic venting into the chimney should be sealed such that the penetration is made airtight (Figure 5).
While it is well understood that flue gas venting must terminate at the exterior, the combustion air pipe is frequently terminated within the mechanical room, the attic, or within an existing combustion air duct (Figures 6, 7). These approaches are not compliant with the FortisBC Furnace and Boiler Replacement Program. The new plastic combustion air pipe is required to terminate on the outside of the building either above the roof or beyond an exterior wall.
The installation of a high-efficiency furnace may result in lower energy bills and a more comfortable home. However, it can also lead to moisture and safety related issues if the unintended consequences of the upgrade are not considered. For example, the installation of new plastic venting often requires additional wall or roof penetrations that must now be waterproofed and airsealed.
The commonly observed practice of sealing the perimeter of new venting at the wall cladding (siding/stucco) is not sufficient - additional weatherization work is required. All new holes in the air/ vapour barrier (polyethene sheet) and moisture barrier (building paper/sheathing membrane) must be sealed to adequately prevent rainwater leaks and air leakage condensation. The recommended detailing for a sidewall vent penetration (exterior and interior) is shown at the end of this document (see Appendix). For further information on the various interactions that can occur between the HVAC system, building enclosure, and other building systems refer to the Best Practices Guide for Air Sealing and Insulation Retrofits³ published by BC Housing.
--------
² Vent systems must be composed of pipe, fittings, cements, and primers that are listed in ULC-S636 - Standard for Type BH Gas Venting Systems
³ Best Practice Guide: Air Sealing and Insulation Retrofits for Single Family Homes available at https://www.bchousing.org