The International Residential Code requires either a Class I or II vapor retarder on the interior side of frame walls in climate zones:5,6,7,8 and marine 4 - refer to the climate zone map on page 16. A vapor retarder is not required for basement walls or on any portion of the wall that is below ground,or on walls made of materials that can't be damaged by moisture or its freezing.
Class III vapor retarders can be used on the interior side of the wall in the following climate zones when any one of the conditions in the table below apply:
Marine 4 |
Vented cladding* over OSBVented cladding* over plywood Vented cladding* over fiberboardVented cladding* over gypsum |
Insulated sheathing with R-value ≥ 2.5 over 2x4 wall |
|
Insulated sheathing with R-value ≥ 3.75 over 2x6 wall |
|
5 |
Vented cladding* over OSB Vented cladding* over plywood Vented cladding* over fiberboardVented cladding* over gypsum |
Insulated sheathing with R-value ≥ 5 over 2x4 wall |
|
Insulated sheathing with R-value ≥ 7.5 over 2x6 wall |
|
6 |
Vented cladding* over fiberboard Vented cladding* over gypsum |
Insulated sheathing with R-value ≥ 7.5 over 2x4 wall |
|
Insulated sheathing with R-value ≥ 11.25 over 2x6 wall |
|
7 & 8 |
Insulated sheathing with R-value ≥ 10 over 2x4 wall |
Insulated sheathing with R-value ≥ 15 over 2x6 wall |