9.36.2.5.(1) & (2) Continuity of Insulation

Figure Source: Alberta Building Code 2014


9.36.2.5. (1) Except as provided in Sentences (2) to (9) and in Sentence 9.36.2.4.(3) regarding balcony and canopy slabs, and except for clearances around components required for fire safety reasons, interior building components that meet building envelope components and major structural members that partly penetrate the building envelope shall not break the continuity of the insulation and shall not decrease the effective thermal resistance at their projected area to less than that required in Articles 9.36.2.6. and 9.36.2.8.

9.36.2.5. (2) Where an interior wall, foundation wall, firewall, party wall or structural element penetrates an exterior wall or insulated roof or ceiling and breaks the continuity of the plane of insulation, the penetrating element shall be insulated

a) on both of its sides, inward or outward from the building envelope, for a distance equal to 4 times its uninsulated thickness to an effective thermal resistance not less than that required for exterior walls as stated in Table 9.36.2.6.A. or 9.36.2.6.B.,

b) within the plane of insulation of the penetrated element to an effective thermal resistance not less than 60% of that required for the penetrated element, or

c) within itself to an effective thermal resistance not less than that required for the penetrated element.