3.1.6. |
Tents and Air-Supported Structures
(See Note A-3.1.6.)
|
3.1.6.1. |
Means of Egress
- Tents and air-supported structures shall conform to Sections 3.3. and 3.4.
|
3.1.6.2. |
Restrictions
- An air-supported structure shall not be located above the first storey on any building.
- An air-supported structure shall not be used for Groups B, C, or Group F, Division 1 major occupancies or for classrooms.
- An air-supported structure shall be designed as open floor space without interior walls, mezzanines, intermediate floors or similar construction.
|
3.1.6.3. |
Clearance to Other Structures
- Except as permitted by Sentences (2), (3) and (4), every tent and air-supported structure shall conform to Subsection 3.2.3.
- Tents and air-supported structures
- shall not be erected closer than 3 m to other structures on the same property except as permitted by Sentences (3) and (4), and
- shall be sufficiently distant from one another to provide an area to be used as a means of emergency egress.
- Tents and air-supported structures not occupied by the public
- need not be separated from one another, and
- are permitted to be erected less than 3 m from other structures on the same property provided this spacing does not create a hazard to the public.
- Tents not more than 120 m2 in ground area, located on fair grounds or similar open spaces, need not be separated from one another provided this does not create a hazard to the public.
|
3.1.6.4. |
Clearance to Flammable Material
- The ground enclosed by a tent or air-supported structure and not less than 3 m of ground outside the structure shall be cleared of all flammable material or vegetation that will spread fire.
|
3.1.6.5. |
Flame Resistance
- Every tent and air-supported structure and all tarpaulins and decorative materials used in connection with these structures shall conform to CAN/ULC-S109, "Flame Tests of Flame-Resistant Fabrics and Films."
|
3.1.6.6. |
Emergency Air Supply
- An air-supported structure used as a place of assembly for more than 200 persons shall have either
- an automatic emergency engine-generator set capable of powering one blower continuously for 4 h, or
- a supplementary blower powered by an automatic internal combustion engine.
|
3.1.6.7. |
Electrical Systems
- The electrical system and equipment in a tent or air-supported structure, including electrical fuses and switches, shall be inaccessible to the public.
- Cables on the ground in areas used by the public in a tent or air-supported structure shall be placed in trenches or protected by covers to prevent damage from traffic.
|