3.6.3. |
Vertical Service Spaces and Service Facilities |
3.6.3.1. |
Fire Separations for Vertical Service Spaces
- Except as provided in Articles 3.6.3.3. and 3.6.3.5. and Section 3.5., a vertical service space shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.6.3.1. for the fire-resistance rating required by Subsection 3.2.2. for
- the floor assembly above the storey, or
- the floor assembly below the storey, if there is no floor assembly above. (See Note A-3.6.3.1.(1).)
Table 3.6.3.1.
Fire Separations for Vertical Service Spaces
Forming Part of Sentence 3.6.3.1.(1)
- A vertical service space that does not extend through the roof of a building shall be enclosed at the top with construction having a fire-resistance rating not less than that required for the vertical service space walls.
- A vertical service space that does not extend to the bottom of a building shall be enclosed at the lowest level with construction having a fire-resistance rating not less than that required for the vertical service space walls.
- A vent from a vertical service space not extending to the roof shall be enclosed within the building with construction having a fire-resistance rating not less than that required for the vertical service space walls.
- Only openings that are necessary for the use of the vertical service space shall be permitted through a vertical service space enclosure.
|
3.6.3.2. |
Foamed Plastic Protection
- Foamed plastic insulation in a vertical service space shall be protected in conformance with Article 3.1.5.14.
|
3.6.3.3. |
Linen and Refuse Chutes
- A linen chute or refuse chute shall
- be impervious to moisture,
- have a smooth internal surface,
- be corrosion-resistant,
- be constructed of noncombustible material, and
- be located in a shaft in which there are no services other than noncombustible drain, waste and vent piping or noncombustible water piping.
- A shaft containing a linen chute or refuse chute shall have a fire-resistance rating conforming to Sentence 3.6.3.1.(1), but not less than
- 1 h if the chute outlet for the discharge room is protected by an automatic, self-latching closure held open by a fusible link, or
- 2 h if no closure is provided at the chute outlet into the discharge room.
- An interior linen chute or refuse chute shall extend not less than 1 m above the roof and shall be vented above the roof with a vent which
- has an unobstructed area not less than the cross-sectional area of the chute, and
- is equipped with a cover that will open automatically, or that can be opened manually, in the event of a fire in the chute.
- Intake openings for a linen chute or a refuse chute shall
- have an area not more than 60% of the cross-sectional area of the chute, and
- be fitted with closures designed to close automatically and latch after use.
- Intake openings for a linen chute or a refuse chute shall be located in rooms or compartments that
- have no dimension less than 750 mm,
- are separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 45 min,
- are designed for no other purpose, and
- do not open directly into an exit.
- Sprinklers shall be installed at the top of each linen chute or refuse chute, at alternate floor levels and in the room or bin into which the chute discharges.
- The room into which a linen chute discharges shall be separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 1 h.
- A refuse chute shall be equipped at the top with spray equipment for washing-down purposes.
- A refuse chute shall discharge only into a room or bin separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h.
- The room or bin into which a refuse chute discharges shall be of sufficient size to contain the refuse between normal intervals of emptying, be impervious to moisture and be equipped with a water connection and floor drain for washing-down purposes.
- A room into which a refuse chute discharges shall contain no service equipment that is not related to refuse handling and disposal.
|
3.6.3.4. |
Exhaust Duct Negative Pressure
- If a vertical service space contains an exhaust duct that serves more than one fire compartment,
- the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure, and
- the individual fire compartments shall not have individual fans that exhaust directly into the duct in the vertical service space.
|
3.6.3.5. |
Grease Duct Enclosures (See Note A-3.6.3.5.)
- Except as provided in Sentence (2), fire separations enclosing grease ducts for commercial cooking operations shall conform to NFPA 96, "Ventilation Control and Fire Protection of Commercial Cooking Operations."
- The fire-resistance rating of field-applied and factory-built grease duct enclosure assemblies shall be determined in conformance with CAN/ULC-S144, "Fire Resistance Test - Grease Duct Assemblies."
|