3.6.3. Vertical Service Spaces and Service Facilities

3.6.3. Vertical Service Spaces and Service Facilities
3.6.3.1.
    Fire Separations for Vertical Service Spaces
  1. Except as provided in Articles 3.6.3.3. and 3.6.3.5. and Section 3.5., a vertical service space shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.6.3.1. for the fire-resistance rating required by Subsection 3.2.2. for
    1. the floor assembly above the storey, or
    2. the floor assembly below the storey, if there is no floor assembly above. (See Note A-3.6.3.1.(1).)

      Table 3.6.3.1.
      Fire Separations for Vertical Service Spaces

      Forming Part of Sentence 3.6.3.1.(1)

  2. A vertical service space that does not extend through the roof of a building shall be enclosed at the top with construction having a fire-resistance rating not less than that required for the vertical service space walls.
  3. A vertical service space that does not extend to the bottom of a building shall be enclosed at the lowest level with construction having a fire-resistance rating not less than that required for the vertical service space walls.
  4. A vent from a vertical service space not extending to the roof shall be enclosed within the building with construction having a fire-resistance rating not less than that required for the vertical service space walls.
  5. Only openings that are necessary for the use of the vertical service space shall be permitted through a vertical service space enclosure.
3.6.3.2.
    Foamed Plastic Protection
  1. Foamed plastic insulation in a vertical service space shall be protected in conformance with Article 3.1.5.14.
3.6.3.3.
    Linen and Refuse Chutes
  1. A linen chute or refuse chute shall
    1. be impervious to moisture,
    2. have a smooth internal surface,
    3. be corrosion-resistant,
    4. be constructed of noncombustible material, and
    5. be located in a shaft in which there are no services other than noncombustible drain, waste and vent piping or noncombustible water piping.
  2. A shaft containing a linen chute or refuse chute shall have a fire-resistance rating conforming to Sentence 3.6.3.1.(1), but not less than
    1. 1 h if the chute outlet for the discharge room is protected by an automatic, self-latching closure held open by a fusible link, or
    2. 2 h if no closure is provided at the chute outlet into the discharge room.
  3. An interior linen chute or refuse chute shall extend not less than 1 m above the roof and shall be vented above the roof with a vent which
    1. has an unobstructed area not less than the cross-sectional area of the chute, and
    2. is equipped with a cover that will open automatically, or that can be opened manually, in the event of a fire in the chute.
  4. Intake openings for a linen chute or a refuse chute shall
    1. have an area not more than 60% of the cross-sectional area of the chute, and
    2. be fitted with closures designed to close automatically and latch after use.
  5. Intake openings for a linen chute or a refuse chute shall be located in rooms or compartments that
    1. have no dimension less than 750 mm,
    2. are separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 45 min,
    3. are designed for no other purpose, and
    4. do not open directly into an exit.
  6. Sprinklers shall be installed at the top of each linen chute or refuse chute, at alternate floor levels and in the room or bin into which the chute discharges.
  7. The room into which a linen chute discharges shall be separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 1 h.
  8. A refuse chute shall be equipped at the top with spray equipment for washing-down purposes.
  9. A refuse chute shall discharge only into a room or bin separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h.
  10. The room or bin into which a refuse chute discharges shall be of sufficient size to contain the refuse between normal intervals of emptying, be impervious to moisture and be equipped with a water connection and floor drain for washing-down purposes.
  11. A room into which a refuse chute discharges shall contain no service equipment that is not related to refuse handling and disposal.
3.6.3.4.
    Exhaust Duct Negative Pressure
  1. If a vertical service space contains an exhaust duct that serves more than one fire compartment,
    1. the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure, and
    2. the individual fire compartments shall not have individual fans that exhaust directly into the duct in the vertical service space.
3.6.3.5.
    Grease Duct Enclosures (See Note A-3.6.3.5.)
  1. Except as provided in Sentence (2), fire separations enclosing grease ducts for commercial cooking operations shall conform to NFPA 96, "Ventilation Control and Fire Protection of Commercial Cooking Operations."
  2. The fire-resistance rating of field-applied and factory-built grease duct enclosure assemblies shall be determined in conformance with CAN/ULC-S144, "Fire Resistance Test - Grease Duct Assemblies."