3.9.2. Building Fire Safety

3.9.2. Building Fire Safety
3.9.2.1.
    Building Area
  1. For the purpose of applying the requirements of Subsections 3.2.1. and 3.2.2. to self-service storage buildings, building area shall mean
    1. the building area of each building, or
    2. the total of the building areas of all buildings as a group. (See Note A-3.9.2.1.(1).)
3.9.2.2.
    Spatial Separation
    (See Note A-3.9.2.2.)
  1. Except as provided in Sentence (3), the spatial separation requirements in Subsection 3.2.3. shall apply to self-service storage buildings.
  2. The distance between each group of self-service storage buildings shall be not less than 9 m.
  3. Subsection 3.2.3. need not apply between buildings within a group of self-service storage buildings, where the distance between these buildings is at least 6 m.
3.9.2.3.
    Access Route
  1. Where Clause 3.9.2.1.(1)(b) is applied to a group of buildings, Article 3.2.5.4. and Sentence 3.2.5.5.(1) shall apply to that group of buildings as if they were a single building.