9.10.1. Definitions and Application

9.10.1. Definitions and Application
9.10.1.1. Sloped Roofs
  1. For the purposes of this Section, roofs with slopes of 60° or more to the horizontal that are adjacent to a room or space intended for occupancy shall be considered as a wall.
9.10.1.2. Testing of Integrated Fire Protection and Life Safety Systems
  1. Where life safety and fire protection systems and systems with fire protection and life safety functions are integrated with each other, they shall be tested as a whole in accordance with CAN/ULC-S1001, "Integrated Systems Testing of Fire Protection and Life Safety Systems," to verify that they have been properly integrated. (See Note A-3.2.9.1.(1).)
9.10.1.3, Items under Part 3 Jurisdiction
  1. Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3.
  2. Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3.
  3. Basements containing more than 1 storey or exceeding 600 m2 in area shall conform to Part 3.
  4. Where rooms or spaces are intended for the storage, manufacture or use of hazardous or explosive material, such rooms or spaces shall conform to Part 3. (See Note A-3.3.1.2.(1).)
  5. Except as provided in Article 3.3.5.8., facilities for the dispensing of fuel shall not be installed in any building.
  6. Openings through floors that are not protected by shafts or closures shall be protected in conformance with Subsection 3.2.8. (See also Sentence 9.9.4.7.(1).)
  7. Chutes and shafts shall conform to Subsection 3.6.3. except where they are entirely contained within a dwelling unit.
  8. Sprinkler systems shall be designed, constructed and installed in conformance with Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17.
  9. Standpipe and hose systems shall be designed, constructed and installed in conformance with Articles 3.2.5.8. to 3.2.5.11. and 3.2.5.17.
  10. Fire pumps shall be installed in conformance with Articles 3.2.5.17. and 3.2.5.18.
  11. Where fuel-fired appliances are installed on a roof, such appliances shall be installed in conformance with Article 3.6.1.5.
9.10.1.4. Items under Part 6 Jurisdiction
  1. In kitchens containing commercial cooking equipment used in processes producing grease-laden vapours, the equipment shall be designed and installed in conformance with Article 6.3.1.7. (See Note A-9.10.1.4.(1).)