9.22.5. Hearth

9.22.5. Hearth
9.22.5.1. Hearth Extension
  1. Except as required in Sentence (2), fireplaces shall have a non-combustible hearth extending not less than 400 mm in front of the fireplace opening and not less than 200 mm beyond each side of the fireplace opening.
  2. Where the fire chamber floor is elevated more than 150 mm above the hearth, the dimension of the hearth measured perpendicular to the plane of the fireplace opening shall be increased by not less than
    1. 50 mm for an elevation above 150 mm and not more than 300 mm, and
    2. b) an additional 25 mm for every 50 mm in elevation above 300 mm.
9.22.5.2. Support of Hearth
  1. Except as permitted in Sentence (2), the fire chamber floor and hearth shall be supported on a reinforced concrete slab not less than 100 mm thick at its supports and, if cantilevered, not less than 50 mm thick at its unsupported edge.
  2. A hearth for a fireplace with an opening raised not less than 200 mm from a combustible floor is permitted to be supported on that floor provided the requirements of Clauses 5.3.6.5. to 5.3.6.7. of CAN/CSA-A405-M, "Design and Construction of Masonry Chimneys and Fireplaces," are followed.