6.7.1. Piping for Heating and Cooling Systems

6.7.1. Piping for Heating and Cooling Systems
6.7.1.1. Piping Materials and Installation
  1. Piping shall be made from materials designed to withstand the effects of temperatures and pressures that may occur in the system.
    (See Articles 3.1.5.19., 3.1.9.1., 9.10.9.6. and 9.10.9.7. for fire safety requirements.)
  2. Every pipe used in a heating or air-conditioning system shall be installed to allow for expansion and contraction due to temperature changes.
  3. Supports and anchors for piping in a heating or air-conditioning system shall be designed and installed to ensure that undue stress is not placed on the supporting structure.
6.7.1.2. Clearances
  1. Clearances between combustible material and bare pipes carrying steam or hot water shall conform to Table 6.7.1.2.

Table 6.7.1.2.
Clearance Between Steam or Hot Water Pipes and Combustible Material

Forming Part of Articles 6.4.2.1. and 6.7.1.2., and Sentence 6.4.3.1.(2)

6.7.1.3. Surface Temperature
  1. The exposed surface temperature of a steam or hot water radiator shall not exceed 70°C unless precautions are taken to prevent human contact.
    (See Note A-6.5.1.1.(3).)
6.7.1.4. Protection
  1. Where a pipe carrying steam or hot water at a temperature above 120°C passes through a combustible floor, ceiling or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than 50 mm larger in diameter than the pipe.
6.7.1.5. Piping in Shafts
  1. Where piping for heating or air-conditioning systems is enclosed in a shaft, the requirements of Article 3.6.3.1. for shafts shall apply.