9.36.2.5.(5) Continuity of Insulation

Figure Source: Alberta Building Code 2014


9.36.2.5. (5) Except as provided in Sentences (8) and (9), where two planes of insulation are separated by a building envelope assembly and cannot be physically joined, one of the plans of insulation shall be extended for a distance equal to at least 4 times the thickness of the assembly separating the two planes.