9.10.21. Fire Protection for Construction Camps

9.10.21. Fire Protection for Construction Camps
9.10.21.1. Requirements for Construction Camps
  1. Except as provided in Articles 9.10.21.2. to 9.10.21.9., construction camps shall conform to Subsections 9.10.1. to 9.10.20.
9.10.21.2. Separation of Sleeping Rooms
  1. Except for sleeping rooms within dwelling units, sleeping rooms in construction camps shall be separated from each other and from the remainder of the building by a fire separation having not less than a 30 min fire-resistance rating.
9.10.21.3. Floor Assemblies between the First and Second Storey
  1. Except in a dwelling unit, a floor assembly in a construction camp building separating the first storey and the second storey shall be constructed as a fire separation having not less than a 30 min fire-resistance rating.
9.10.21.4. Walkways Connecting Buildings
  1. Walkways of combustible construction connecting buildings shall be separated from each connected building by a fire separation having not less than a 45 min fire-resistance rating.
9.10.21.5. Spatial Separations
  1. Construction camp buildings shall be separated from each other by a distance of not less than 10 m except as otherwise permitted in Subsections 9.10.14. and 9.10.15.
9.10.21.6. Flame-Spread Ratings
  1. Except in dwelling units and except as provided in Sentence (2), the surface flame-spread rating of wall and ceiling surfaces in corridors and walkways, exclusive of doors, shall not exceed 25 over not less than 90% of the exposed surface area and not more than 150 over the remaining surface area.
  2. Except within dwelling units, corridors that provide access to exit from sleeping rooms and that have a fire-resistance rating of not less than 45 min shall have a flame-spread rating conforming to the appropriate requirements in Subsection 9.10.17.
9.10.21.7. Smoke Detectors
  1. Except in dwelling units, corridors providing access to exit from sleeping rooms in construction camp buildings with sleeping accommodation for more than 10 persons shall be provided with a smoke detector connected to the building alarm system.
9.10.21.8. Portable Fire Extinguishers
  1. Each construction camp building shall be provided with portable fire extinguishers in conformance with the appropriate provincial or territorial regulations or municipal bylaws or, in the absence of such regulations or bylaws, in conformance with the NFC.
9.10.21.9. Hose Stations
  1. Every construction camp building providing sleeping accommodation for more than 30 persons shall be provided with a hose station that is protected from freezing and is equipped with a hose of sufficient length so that every portion of the building is within reach of a hose stream.
  2. Hose stations required in Sentence (1) shall be located near an exit.
  3. Hoses referred to in Sentence (1) shall be not less than 19 mm inside diam and shall be connected to a central water supply or to a storage tank having a capacity of not less than 4 500 L with a pumping system capable of supplying a flow of not less than 5 L/s at a gauge pressure of 300 kPa.